Guangzhou Fortune Power Co., Ltd. National Hotline: 86-020-62861639
Conditions of use and the environment
1. The charging current (float use): 0.15CA following
2. Discharge current range: 0.05CA ~ 3CA
3. Ambient temperature: 0 ℃ ~ 40 ℃ (suitable temperature is 25 ℃)
4. Charge voltage: (12V battery recommended)
Ambient temperature
Charging voltage (float use)
Discharge voltage (float use)
25 ℃
13.60 to 13.80V
10.5V
Notes: 1. When using the float, when the charge current exceeds 0.15CA, please consult in advance with the company.
2.0.15CA = 0.15 × battery capacity, 0.05CA and 3CA so on.
Storage charging conditions
Storage temperature range is -15 ℃ ~ 40 ℃, the battery should be regularly supplementary charge: no charge during the relationship and be able to keep the temperature as follows:
Below 20 ℃: 9 months
The following 20 ~ 30 ℃: 6 months
30 ~ 40 ℃ following: 3 months